TABLE
SHOWING THE CHOICE OF THE SUITABLE MODEL OF RECUPARATOR ACCORDING
TO THE THERMAL CAPACITY OF THE BOILER AND THE AMOUNT OF BURNT COMBUSTIBLE
PER YEAR
(in
the table we have considered the CO2 of 9,5 with the temperature
of the output fumes from the boiler of 250°C)
|
MODEL
|
ECO
6 N
|
ECO
12 N
|
ECO
18 SP
|
ECO
24 SP
|
ECO
28 SP
|
ECO
P
18-2
|
ECO
P
18-3
|
ECO
P
28-3
|
boiler
KCAL/H
|
from
|
8.000
|
20.000
|
40.000
|
80.000
|
120.000
|
180.000
|
300.000
|
450.000
|
to
|
20.000
|
40.000
|
80.000
|
120.000
|
180.000
|
300.000
|
450.000
|
600.000
|
Combustible
consumption
|
Diesel
oil
KG per year
|
3.500
|
6.500
|
10.000
|
20.000
|
30.000
|
50.000
|
85.000
|
130.000
|
methane
MC per year
|
4.200
|
78.000
|
12.000
|
24.000
|
36.000
|
60.000
|
102.000
|
156.000
|
KCAL/H
recuperated
|
2.371
|
5.072
|
7.804
|
15.000
|
21.000
|
39.000
|
66.000
|
101.000
|
Warm
water
produced
/\T
58° L/H
|
41
|
76
|
118
|
235
|
340
|
558
|
1.000
|
1.530
|
Output
fumes from recuperator °C
|
120
|
120
|
120
|
120
|
120
|
120
|
120
|
120
|
N.
plates
|
4
|
8
|
12
|
16
|
22
|
36
|
54
|
84
|
surface
MQ
|
1
|
2
|
3
|
4
|
5,5
|
9
|
13,5
|
21
|
content
LT
|
1,48
|
2,96
|
4,44
|
5,92
|
8,14
|
13,3
|
20
|
31
|
Capacity
with /\T 10° L/H
|
273
|
507
|
780
|
1.500
|
2.100
|
3.900
|
6.600
|
10.100
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TECHNICAL
DATA REGARDING ECO-FEA RECUPERATORS
Switch
surface per plate: 0,25MQ
Plate content: 0,370 LITRES
Loss of head: 350 mm
Max working temperature: 550°C
Max allowable pressure: 4 ATM
|
|
|
|
|
|
|
|
|
|
OVERALL
AND CONNECTIONS DIMENSIONS
|
|
|
|
MODEL
|
A
|
B
|
C
|
D
|
connections
|
|
ECO
6 N
|
250
|
776
|
320
|
160
|
1"
|
ECO
12 N
|
430
|
776
|
320
|
160
|
1"
|
ECO
18 SP
|
610
|
776
|
320
|
200
|
1"
|
ECO
24 SP
|
790
|
776
|
320
|
250
|
1
1/4"
|
ECO
28 SP
|
1060
|
776
|
320
|
250
|
1
1/4"
|
ECO
P 18-2
|
880
|
1552
|
320
|
300
|
1
1/4"
|
ECO
P 18-3
|
880
|
2328
|
320
|
350
|
1
1/4"
|
ECO
P 28-3
|
1330
|
2328
|
320
|
400
|
1
1/4"
|
|
APPROBATION
OF MINISTRY OF INDUSTRY.
OUR
EQUIPMENTS ARE MODULAR.
|
Fea
produces special recuperators suitable for particular applications
of energy recovery.
|
Fea
technical service is at Customers' disposal throughout Italy for
suggestions and analysis necessary for installing recuperators.
|
|
Data
are not binding for Fea. Fea reserves the right to make any changes
which might be deemed necessary.
|
|
|